Variable refrigerant flow systems: A2L refrigerant safety, system and piping design, and equipment

Design and application for engineers and contractors

63.5–185.5 min PDH

About this presentation

A three-part seminar on variable refrigerant flow (VRF) systems for consulting engineers, code reviewers and contractors. Part one explains why new VRF systems are moving to R-32 under EPA's Technology Transitions rule, what the A2L safety class means, how ASHRAE 15, UL 60335-2-40 and the mechanical codes adopted in Pennsylvania, New Jersey, Delaware and New York fit together, and how to apply the ASHRAE 15 method, from room charge limits to detection, shutoff valves and ventilated enclosures. It works the method through an office and a hotel, then covers ceiling voids, machinery rooms, shafts, exit paths, institutional occupancies and installation. Part two covers system and piping design: heat pump and heat recovery, selection, operating range, piping limits and installation practice, how layout drives the refrigerant charge, and ventilation with VRF. Part three surveys one manufacturer's current product family, R-32 except the water-cooled line: outdoor units with their capacity and temperature ranges, indoor units, branch selector and shutoff valve boxes, air handler integration kits for standard and dedicated outdoor air duty, and controls, with dedicated outdoor air units from two other manufacturers that pair with it.

Learning objectives

  1. Explain why new VRF is moving to R-32 and which EPA dates apply.
  2. Describe the ASHRAE 34 safety groups and R-32's flammability limits.
  3. Identify the code and ASHRAE 15 edition each local jurisdiction enforces.
  4. Calculate a room's charge limit and a circuit's releasable charge.
  5. Select mitigation: detection, shutoff valves, openings or enclosures.
  6. Apply the machinery-room, shaft, exit-path, institutional and installation rules.

Topics

  • variable refrigerant flow
  • VRF
  • R-32
  • A2L refrigerants
  • refrigerant safety
  • ASHRAE 15
  • ASHRAE 34
  • UL 60335-2-40
  • AIM Act
  • EPA Technology Transitions
  • global warming potential
  • mechanical code
  • effective dispersal volume charge
  • releasable charge
  • refrigerant detection
  • safety shutoff valve
  • ventilated enclosure
  • connected spaces
  • machinery room
  • refrigerant shaft
  • institutional occupancy
  • branch selector box
  • heat recovery
  • connection ratio
  • refrigerant piping
  • oil return
  • brazing
  • pressure testing
  • evacuation
  • refrigerant charge calculation
  • low-ambient cooling
  • cold-climate heat pump
  • water-cooled VRF
  • DOAS
  • ventilation
  • AHU integration kit
  • hot-gas reheat
  • BACnet