Harmonics and power qualityVariable-speed fan and pump control
Variable frequency drives and harmonics: how drives work and how to meet IEEE 519 in buildings
Application, harmonic mitigation, matrix converters and harmonic analysis
About this presentation
A seminar for consulting engineers, owners and contractors on variable frequency drives in building HVAC and the harmonic current they draw. It explains how a six-pulse PWM drive turns fixed-frequency power into variable speed, what variable speed saves once a system has control head, and why the drive's rectifier draws harmonic current; how harmonics heat equipment, distort voltage, most of all on standby generators, and lower true power factor; how reactors, multipulse drives, passive and active filters, active front ends and matrix converters compare; and how IEEE 519 judges a facility at the point of common coupling, with a worked hospital example, so that a harmonic analysis can size mitigation before it is specified. The full version adds energy-code requirements, multiple motors, enclosures and long motor leads, a step-by-step look at how a matrix converter builds its output and how far its output voltage reaches in theory and in practice, and the 2014 and 2022 revisions of IEEE 519.
Learning objectives
- Explain how a PWM drive makes variable speed, and why its rectifier draws harmonic current.
- Select bypass and disconnect arrangements for fan and pump drives.
- Explain how harmonic current heats equipment, distorts voltage on utility and generator power, and lowers true power factor.
- Compare harmonic mitigation methods, from reactors to matrix converters, by input distortion, light-load behavior and generator compatibility.
- Apply IEEE 519 at the correct point of common coupling using total demand distortion and the short-circuit ratio, and use a harmonic analysis to size mitigation.